Performance of Neutral Grounding Resistance and Solid Grounding on 60 MVA Power Transformer

Authors

  • Zuraidah Tharo University of Pembangunan Panca Budi Medan
  • Amani Darma Tarigan University of Pembangunan Panca Budi Medan
  • Siti Anisah University of Pembangunan Panca Budi Medan
  • David Banjarnahor University of Pembangunan Panca Budi Medan

DOI:

https://doi.org/10.53893/ijrvocas.v2i4.172

Keywords:

Neutral Grounding Resistance, Grounding Solid, Comparison, Power Transformer 60MVA

Abstract

This research will look at the protection system on a 60 MVA power transformer and compare two grounding systems, namely grounding with Neutral Grounding Resistance (NGR) and Grounding Solid (GS). The performance of the two systems will be seen, which is the most effective and efficient. Soil resistance is directly related to water content and temperature; thus, it can be assumed that the resistance of a grounding system will change according to climate change. To obtain a stable grounding resistance, the grounding electrode is installed at the optimal depth to achieve a constant level of water content. The study began by collecting data and then comparing grounding using NGR with GS and measuring the resistance values ​​of NGR and GS on a 60 MVA Power Transformer. The results of this comparison will obtain data on the NGR and GS resistance values ​​on the 60 MVA power transformer, then analyze and compare these values ​​which will provide a conclusion which of the two systems has the best value for grounding.

 

Author Biographies

Zuraidah Tharo, University of Pembangunan Panca Budi Medan

 

 

 

Amani Darma Tarigan, University of Pembangunan Panca Budi Medan

 

 

Siti Anisah, University of Pembangunan Panca Budi Medan

 

 

David Banjarnahor, University of Pembangunan Panca Budi Medan

 

 

References

Standar IEEE Std 519-1992. (1993). Recommended Practices arul Requirements for Harmonis Control inElectrical Power Systems. New York: 1992-1993

Hutauruk, T. (1991). Pengetanahan Netral Sistem Tenaga & Pengetanahan Peralatan. Jakarta. Erlanga.

Anggoro, Budi. (2002). Sistem Kelistrikan. Jakarta. Media Pustaka Pratama.

Habibirahim. (2012). Perhitungan Tahanan Pentanahan Dengan Konfigurasi Bujur Sangkar. Palembang. Politeknik Negeri Sriwijaya

I. G. D. A. I. W. R. I Gusti Agung Putra Sanjaya, “Analisis Setting Pengaman Transformator Daya Di Gardu Induk Nusa Dua Jika Terjadi Gangguan Hubung Singkat Satu Phasa Tanah,” E-Journal Spektrum Vol.4, pp. 28-31, 2017.

N. Pamudji, Pedoman Trafo Tenaga, Jakarta: PT.PLN (Persero), 2014.

R. T. Samalo, Analisis Sistem Pentanahan Pada Transformator Daya 60 MVA di GI Duri Kosambi, Jakarta: Sekolah Tinggi Teknik-PLN, 2017

T. S. T. O. Moh.Madani, “Analisa Setting Over Current Relay (OCR) dn Ground Fault Relay (GFR) Pada Trafo 60 MVA di GIS 150 KV Simpang,” Seminar Nasional Sains dan Teknologi Terapan VII 2019, pp. 685-686, 2019.

S. A. B. Dedi Mirza, “Analisa Pengaruh Neutral Ground Resistant (NGR) 40 Ohm Pada Transformator Daya 30 MVA Di Gardu Induk Bireuen Terhadap Arus Gangguan Satu Fasa Ke Tanah,” Jurnal Energi Elektrik Volume 7, 2018.

M. D. Kuncahyo, Analisis Setting Ground Fault Relay (GFR) Terhadap Sistem Pentanahan Netral Transformator Menggunakan Metode Neutral Grounding Resistor (NGR) pada Penyulang PLN Rayon Kuala Pembuang Kalimantan Tengah, Malang: Institut Teknologi Nasional Malang, 2017

PT.PLN (Persero), Pedoman Supervisi Kontruksi Jaringan, Transmisi dan Gardu Induk, Jakarta: PT.PLN (Persero).

PT. PLN. (Persero), Proteksi dan Kontrol Transformator, Jakarta: PT.PLN (Persero).

M. Ir. Wahyudi Sarimun N., Proteksi Sistem Distribusi Tenaga Listrik, Depok: Garamond, 2016

Fachmi, Muhammad Kharish. (2017). Analisis Sistem Pentanahan NGR (Neutral Grounding Resistant) Jenis Liquid Dan Solid Pada Trafo Tenaga. Jakarta. Universitas Pendidikan Indonesia.

Karmain, J, and Felienty, (1995) Sistem Pengaman Tenaga Listrik, Sistem Pengaman Tenaga Listrik Jawa Bali. Jurnal Teknik Elektro, Vol. 1, No. 1, diakses Agustus 2019 ISSN 2622 – 7002 (online), https://doi.org/10.30596/rele.v1i1.2257

Additional Files

Published

2023-01-28

How to Cite

Tharo, Z., Tarigan, A. D., Anisah, S., & Banjarnahor, D. (2023). Performance of Neutral Grounding Resistance and Solid Grounding on 60 MVA Power Transformer. International Journal of Research in Vocational Studies (IJRVOCAS), 2(4), 86–93. https://doi.org/10.53893/ijrvocas.v2i4.172